89
Configuration
Menu item
Action
Choices
Select process
variable
(CHANNEL)
Select desired process
variable using
keys.
Press enter to confirm.
Limit 2 function
(FUNCTION)
Select desired function
using
keys.
Press enter to confirm.
Limit 2 icon:
Limit 2 contact type
(CONTACT)
N/O: normally open
contact
N/C: normally closed
contact
Select using
keys.
Press enter to confirm.
Limit 2 setpoint
(LEVEL)
Enter setpoint using
keys.
Press enter to confirm.
Within meas. range
Limit 2 hysteresis
(HYSTERESIS)
Select hysteresis using
keys.
Press enter to confirm.
0 ... 50 % full scale
Limit 2 delay
(DELAYTIME)
The contact is activated
with delay (deactivated
without delay)
Adjust delay using
keys.
Press enter to confirm.
0...9999 SEC
(0010 SEC)
Limit Lo
Hyst
Setpoint
Contact
0
1
Signal
Limit Hi
Hysteresis -
Signal
Setpoint
Contact
0
1
Summary of Contents for Stratos Pro A401B CONDI