If the lance is located below the distributor it is necessary to provide a separate dehydration of the distributor
and the lance heating line.
Figure No. 28
Connection of the steam humidifier, when the lance is located below the distributor
NOTE! The diagrams listed above do not represent all required connections
c)
Humidifier with an electrical
steam generator
The steam generator should be connected according to the picture
Figure No. 29
Connection of water supply and return from the humidifier with an electrical steam generator
Requirements:
1.It is required to install a cut-off valve and mechanical filter (not provided) at the supply line.
2.The water return pipes going out from the cylinder must be able to withstand
100
°
C
3.It is necessary to ensure an appropriate decline of the water return pipes (at least 5
°
)
4.The pipeline diameters are selected based on the generator manufacturer's recommendations.
5.A drain trap should be installed at the return water pipe or it is necessary to arrange the pipe in such a way to
obtain a drain trap-shape.
6.Connection of the steam generator and the lance can be done only with dedicated pipes supplied with the hu-
midifier.
7.While arranging the lance supply pipes do not allow to form drain traps and narrowing of cross-section. Figure
No. 30
Figure No. 30
Strainer filter
Duct cross-section
Reverse dehydrator
Reverse dehydrator
Inclination 5
°
Inclination 5
°
Water drainage
Supply
Shut-off valve
Filter
Drain trap
No
No