97 / 97
83001602.Kf
No.: Explanation
Annual
Six-
monthly
as
required
Remark
Tank / water tank
80 Optical check for dirt, damage and corrosion
x
81 Check fixing
x
82 Check level
x
Control cabinet
90 Optical check for dirt, damage and corrosion
x
x
91 Check fixing
x
92 Check all threaded connections
x
93 Check all indicator lights and error messages
x
94 Check the temperature and pressure sensors are
functioning properly
x
95 Check the function of the motor protection switches
x
96 Check 24 VDC and supply voltage
x
x
97 Check control cabinet heater
x
99 Check control cabinet filter and if necessary
replace/clean
x
Documents and labelling
110 All documents such as operating instructions,
diagrams, circuit plans, system log are present
x
x
111 Rating plate and labels are clearly legible
x
x
Battery - time/date
120 Battery
x
Every 5
years
Leakage control of the refrigeration circuit in
accordance with (EC) 517/2014
x
IV.
Product registration
PDF download at: www.kkt-chillers.com/service/produktregistrierung