Main menu
Information
Settings
Settings
Alarm menu
Limit monitoring
Limit monitoring
Control Panel
Control
Limit temperature cooling water
Software update
Control pump
Time delay
5
min
Datalog export
Control compressor
Outlet temp.
Datalog stop
Chiller configuration
Running delay
15
min
Sensor configuration
Outlet max STOP
32.0
°C
Outlet max warning
30.0
°C
Outlet min STOP
-20.0
°C
Outlet temp. 2
Running delay
5
sec
Outlet max STOP
34.0
°C
Outlet max warning
32.0
°C
Outlet min STOP
15.0
°C
Limit tank pressure
Tank max level
125
mbar
Tank min level warning
105
mbar
Tank min level STOP
80
mbar
Hysteresis
2
mbar
Pressure exp. vessel
Min warning
2.5
bar
Min Stop
2.0
bar
Limit pressure water
Time delay start
20
sek
Time delay running
10
sek
Pressure cooling water (VP)
Min warning
0.5
bar
Min STOP
0.1
bar
Differential pressure
Outlet max STOP
2.0
bar
Pressure pump 1
Outlet max STOP
10.0
bar
Outlet min warning
2.5
bar
Outlet min STOP
2.0
bar
Pressure pump 2
Outlet max STOP
10.0
bar
Outlet min warning
2.5
bar
Outlet min STOP
2.0
bar
Conductivity
Conduc. max. alarm
50
µS/cm
Conduc. max. warning
30
µS/cm