Settings
Limit monitoring
Control
Control
Control pump
Thermost. pump start
Control compressor
Control pump 1
pressure
Basics
Control cold water
temperature
Chiller configuration
Control hot gas bypass
Sensor configuration
Control cold water
valve
Control tank heating
Control EEV
superheating
Control condensation
Control cooling water
Control condensation
Control cooling water
Control ESS free
cooling
Model
Eco
Control tank refill
Setpoint eco mode
31.5
bar
Control conductivity
Setpoint comfort mode
35.0
bar
P-band
10.0
bar
Ti Int time
100
sec
Td diff. time
0
sec
HP max limit
Application point
32.0
bar
End point
38.0
bar
Delay time
Compressor control
Temp. cooling water inlet
Temp. < 30°C
12
sec
Temp. < 40°C
18
sec
Temp. > 40°C
25
sec
Control ESS free cooling
Energy-saving system
AUTO
Diff.temp. ambient-return 3.0
K
Hysteresis
0.5
K
Delay time
300
sec
Sequence
50
%
P-band
3.0
K
Ti Int time
100
sec
Td diff. time
0
sec
Min. limit
Setpoint
10.0
°C
P-band
9.0
K
Ti Int time
100
sec
Td diff. time
0
sec