75 / 97
83000102.Ko
Main menu
Information
Settings
Settings
Alarm menu
Limit monitoring
Control Panel
Control
Software update
Control pump
Datalog export
Control compressor
Control compressor
Datalog stop
Basics
Compressor type
DSH
Chiller configuration
Year of construction
2018
Sensor configuration
Time between 2 starts
300
sec.
Min timeout
5
sec.
Low pressure warning (LP)
LP warning (STOP+dP)
0.2
bar
Time delay
30
sec.
LP STOP
7.3
bar
Delay start
60
sec.
Delay running
3
sec.
LP ON (STOP+dP)
1.5
bar
Number of alarms per hour 3
Time delay
10
sec.
High pressure (HP)
HP warning ON
42.5
bar
HP warning OFF
40.0
bar
Time delay
10
sec.
HP STOP
43.0
bar
HP off
40.0
bar
Time delay
10
sec.
HP max limit
Cooling levels OFF
42.0
bar
Cooling levels ON
40.0
bar
HP-LP difference
Cooling levels OFF
36.8
bar
Cooling levels ON
30.0
bar
Pump out?
No
Compressor LP OFF
2.5
Bar
Pump out timeout
30
sec.
Basics
Chiller type
cBox 30
Year of construction
2020
Compressor type
DSH
AI ambient temp.
No