8.5.2.
Main menu
Figure 20: Main menu
From the Main menu you can move into the submenus or return to the Start screen.
For the structure of the individual submenus see
Fehler! Verweisquelle konnte nicht gefunden werden.
Fehler! Verweisquelle konnte nicht gefunden werden., starting on page Fehler! Textmarke nicht definiert..
The entries of the submenus are either visible or hidden depending on the configuration of the system.
8.5.3.
Information
In the information menu you branch into different submenus, which provide an overview of the current status
of the system:
Measured values
Values of the analogue inputs
Status
States of the digital inputs and outputs as well as some controller internal
states
Energy meter
Operating hours
Operating hours of the individual components of the system
Digital inputs
Status at the terminals of the digital inputs
Digital outputs
Status of the output relays
Analogue inputs
Signal before the analogue-digital converter. The value must be between 0
and 4095. 0 means that no sensor is connected. 4095 means, the input is
short-circuited
Analogue outputs
Signal before the digital-analogue converter. The value 10000 corresponds
to an output voltage of 10 volt
Software status
Test point 1
Error memory
8.5.4.
Settings
All setpoint/target and parameter values and times are stored in the Settings menu.
Limit value monitoring
Regulation
Pump control
Compressor control
Basics
Overview of the fundamental hardware configuration.
System configuration
Sensor configuration