71 / 97
83000102.Ko
Settings
Limit monitoring
Control
Control
Control pump
Thermost. pump start
Control compressor
Control pump 1 pressure
Basics
Control pump 2 pressure
Chiller configuration
Control cold water
temperature
Control hot gas bypass
Sensor configuration
Control hot gas bypass
Start relief
2
sec.
Control cold water valve
Output control 2point
Control tank heating
Valve OPEN
-20
%
Control EEV
superheating
Valve CLOSED
30
%
Control condensation
Continuous output control
Control cooling water
Temp. outlet
Control ESS free cooling
Difference
0.2
K
Control tank refill
Proportional band
2.0
K
Ti integration time
50
sec.
Td diff. time
0
sec.
Temp. min
35.0
°C
Opening temp. min
0
%
Temp. max
40.0
°C
Opening temp. max
100
%
Cold water high temp start ass.
Temp. inlet (VP)
Valve OPEN
40.0
°C
Valve CLOSED
35.0
°C
Control cold water valve
Setpoint
32.0
°C
P-band
10.0
K
Ti Int time
100
sec.
Td diff. time
0
sec.
Control tank heating
Setpoint
8.0
°C
Hysteresis
2.0
K
Control EEV superheating
Start
No
Setpoint
12.0
°C
Delay time
60
sec.
Setpoint
6.0
K
P-band
6.0
K
Ti Int time
400
sec.
Td diff. time
0
sec.
MOP
Application point
10.6
bar
End point
15.6
bar
Opening minimum
100
Inc
Delay start
10
sec.
Delay running
10
sec.
Superheating min
1.5
K
Superheating max
18.0
K
Number of alarms / hour
3
Start
No
Opening minimum
10
%
Delay time
60
sec.