Chapter 2: Installation
KFP-CE4 Series Installation Manual
15
Connecting unsupervised inputs
Connect unsupervised input switches to INPUT1 and INPUT2, as shown in
Figure 4 or Figure 5 on page 11. Nominal resistance values (including any cable
resistance) are shown below.
Table 7: Nominal resistance values for unsupervised inputs
Input function
Activated
Standby
Remote reset command
> 9 kΩ to ≤ 9 kΩ transition
N/A
Extended fire routing delay
≤ 9 kΩ
> 9 kΩ
Fire routing inhibit delay
≤ 9 kΩ
> 9 kΩ
Class change
≤ 9 kΩ
> 9 kΩ
Delays off
≤ 9 kΩ
> 9 kΩ
Connecting supervised inputs
Connect supervised input switches to INPUT1 and INPUT2, as shown in
Figure 8
below.
Figure 8: Connecting supervised inputs
Nominal resistance values (including any cable resistance) are shown in Table 8
below.
Table 8: Nominal resistance values for supervised inputs
Input function
Input
Value
[1]
State
Fire routing acknowledgement
(type 1, 100 seconds)
1
≤ 220 Ω
Short circuit
> 220 Ω to 8 kΩ
Active [2]
> 8 kΩ to 10 kΩ
Fault [3]
> 10 kΩ to 20 kΩ
Standby
> 20 kΩ
Open circuit
Summary of Contents for KFP-CE4 Series
Page 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Page 6: ...iv KFP CE4 Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Page 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Page 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Page 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Page 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...