Appendix A: Configuration presets
KFP-CE4 Series Installation Manual
73
NEN 2575 2E presets
Table 40: Configuration presets
Preset
43
Control panel
T wo evacuation areas
EOL type
Passive
Output type
Class B
Evacuation sounder outputs
4
Fire routing outputs
3
Zone type
Odd: Automatic
Even: Manual
Table 41: Inputs and outputs
Input/Output Standard
EN 54-13
INPUT1
Fire routing inhibit delay
Fire routing acknowledge type1
INPUT2
Delays off
Fault warning open supervision
OUT1
Sounder circuit (activated by a fire
alarm in zone 1 or 2)
Sounder circuit (activated by a fire
alarm in zone 1 or 2)
OUT2
Sounder circuit (activated by a fire
alarm in zone 1 or 2)
OUT3
Sounder circuit (activated by a fire
alarm in
zone 3
or 4)
Sounder circuit (activated by a fire
alarm in
zone 3
or 4)
OUT5
Fire routing ( activated by a automatic
fire alarm device)
Fire routing (activated by automatic or
manual fire alarm device)
OUT
6
Fire routing (activated by a manual fire
alarm device)
NEN 2575 1E presets
Table 42: Configuration presets
Preset
45
Control panel
One evacuation area
EOL type
Passive
Output type
Class B
Evacuation sounder outputs
4
Fire routing outputs
2
Zone type
Odd: Automatic
Even: Manual
Summary of Contents for KFP-CE4 Series
Page 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Page 6: ...iv KFP CE4 Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Page 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Page 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Page 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Page 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...