Chapter 2: Installation
KFP-CE4 Series Installation Manual
17
Table 11: Class A output functionality (for EN 54-13 compliance)
Operating
mode
OUT1/OUT2 OUT3/OUT4 2010-1-SB
[1]
OUT1/OUT2
2010-1-SB
[1]
OUT3/OUT4
2010-1-SB
[2]
OUT3
NEN 2575 with
four evacuation
areas
Evacuation
sounders for
zone
1
Evacuation
sounders for
zone
2
Evacuation
sounders for
zone
3
Evacuation
sounders for
zone
4
Fault warning
NEN 2575 with
two evacuation
areas
Evacuation
sounders for
zone
1 or
zone
2
Evacuation
sounders for
zone
1 or
zone
2
N/A
N/A
Fault warning
NEN 2575 with
one evacuation
area
Evacuation
sounders for
any
zone
Evacuation
sounders for
any
zone
N/A
N/A
Fault warning
[1] 2010-1-SB required in preset 94
[2] 2010-1-SB required in mode 35
Output termination
Output termination is required at all times, whether the output is used or not. The
type of termination depends on the output class, as shown in
Table 12 below.
Table 12: Termination required for output classes
Output class
Output termination
Class B (default)
All outputs require a 15 kΩ end
-of-line resistor for termination. If
an output is not used, the end
-of-line resistor must be installed
across the unused output terminals (see Figure 4 on page 11).
Class A (EN 54-13)
All outputs require a 4.7 kΩ, 1/4W, 1% end
-of-line resistor for
termination. If an output group (OUT1/2, OUT3/4) is not used,
the end-of-line resistor must be installed across the unused
output terminals (see Figure 5 on page 11).
See “
Input and output specifications”
on page 65
for details on voltage and
current ratings.
Output polarity
All outputs are polarity sensitive. Observe polarity or install a 1N4007 diode or
equivalent to avoid inverted activation issues.
Connecting sounders or other notification devices to supervised outputs
Depending on the operating mode, up to four sounder or notification device
circuits can be connected. See Table 10
on page 16
.
Connecting fire routing equipment to supervised outputs
Connect fire routing equipment as shown in Table 13 on page 18.
Summary of Contents for KFP-CE4 Series
Page 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Page 6: ...iv KFP CE4 Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Page 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Page 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Page 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Page 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...