Chapter 3: Configuration and commissioning
48
KFP-CE4 Series Installation Manual
Expansion board output delay
Use this menu to configure an expansion board output delay of up to 10 minutes,
where the feature is available.
To configure an expansion board output delay:
1.
For output 1 on expansion board A, set the display as shown below, and then
press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the
Activated LED on the
expansion board flashes fast to indicate that the module
delay menu is active.
2. Select a value from 00 to 10 using the value selection buttons (2 and 4).
3. Press Enter.
4.
Repeat steps 1 to 3 as required
for each output (1 to 4) on each installed
module (A, B, C, and D) where a delay is required.
5. Save your changes.
Fire network and repeaters configuration
This section describes how to configure a fire network of conventional control
panels in order to:
•
Connect repeaters (any conventional control panel can be configured to
operate as a repeater)
•
Create a fire network of conventional control panels, when you need
additional conventional
zones in your system
•
Create a network including compatible addressable control panels, to add
more features to your fire alarm and evacuation system (e
.g. logging events,
complex output activation controlled by the addressable system, remote
monitoring)
When a conventional panel is connected to a fire network it normally displays the
status of one or more panels in the network (depending on repeater configuration
settings). To display information for only that panel, press the Enter key for 3
seconds to p
rovide a temporary, 30
-second display of the local status indications.
Basic configuration options
The following table shows the options for creating basic fire network (firenet)
configurations.
Summary of Contents for KFP-CE4 Series
Page 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Page 6: ...iv KFP CE4 Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Page 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Page 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Page 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Page 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...