Chapter 4: Maintenance
KFP-CE4 Series Installation Manual
61
Troubleshooting batteries
Battery supply and battery fuse faults are indicated by a flashing Supply Fault
LED. If this LED is flashing, check the following:
•
That the battery cables are in good condition
•
That the battery cables are connected securely and correctly at the battery
and at the control panel PCB
If the cables are in good condition and all connections are correct, then the
batteries should be replaced immediately.
Replacing batteries
Batteries must be replaced periodically as recommended by the battery
manufacturer. The useful life of the battery is approximately four years. Avoid the
total discharge of the batteries. Always use the recommended replacement
batteries.
To replace the batteries:
1.
Disconnect and remove the existing batteries from the cabinet.
2. Install and connect the replacement batteries using the bridge provided.
Observe correct polarity.
3.
Dispose of the batteries as required by local or regional regulations.
Summary of Contents for KFP-CE4 Series
Page 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Page 6: ...iv KFP CE4 Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Page 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Page 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Page 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Page 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...