Installation
35 / 61
2019/11
010-917_SON_EN
Check the function of the actuator valve switchover valve
Carry out the following settings in the
Maintenance
menu:
•
Manual operation
=>
Part empty
, the actuator valve moves the valve into the correct position, then the
pump(s) start(s). If the pump(s) start(s) immediately, the valve was already in the designated position.
•
ESC, the pump(s) is/are switched off =>
Mix
, the actuator valve moves the valve into the opposite position,
then the pump(s) start(s).
•
ESC, the pump(s) is/are switched off =>
Part empty
, the actuator valve moves the valve into the opposite
position, then the pump(s) start(s).
•
ESC, the pump(s) is/are switched off, the actuator valve is ready for operation.
Check the function of the solenoid valve for hot water
1
Carry out the following settings in the
Maintenance
menu:
•
Manual operation
=>
Flush
the solenoid valve is actuated. Make sure that the water runs into the system tank
via the refill inlet.
Check the function of the solenoid valve for cold water
Carry out the following settings in the System control menu:
•
Maintenance
=>
Manual operation
=>
Fill
the solenoid valve is actuated. Make sure that the water runs into the
system tank via the refill inlet.
Check the function of the
SonicControl
Sensor (option)
Carry out the following settings in the System control menu:
•
Maintenance
=>
Manual operation
=>
SonicControl
=>
Start measurement?
=> OK - measurement is carried
out and the result displayed. If not fault message appears, the
SonicControl
sensor is ready for operation.
• Check the function of the remote control (option)
The remote control provides the same operating features as the control unit.
• Carry out initialisation and functional check on the
SonicControl
in accordance with the operating instructions
provided (optional).
System type F is now ready to use.
1) Hot water is recommended