3-2
BOP 5-20DL 081915
Application and test set up diagrams on the following pages show the symbolic and simplified
representation of the four programmable circuits of the BOP:
•
Voltage Control Channel: see Figure 3-2 and PAR. 3.3.1 for local control.
•
(±) I
O
Limit Circuits: See Figure 3-3 and PAR. 3.3.2 for local control.
•
Current Control Channel: see Figure 3-4 and PAR. 3.3.3 for local control.
•
(±) E
O
Limit Circuits: see Figure 3-5 and PAR. 3.3.4 for local control.
The complete simplified diagram is shown in Figure 3-29 at the end of this section. The four cir-
cuits can be programmed separately as described in the examples in this section, or one main
channel and two limit channels can be used simultaneously as the application requires. The two
main bipolar voltage and current channels are manually selected by the front panel MODE
switch.
The numbered terminals in the simplified diagrams of this section correspond to the terminals of
the Rear Programming Connector (see Figure 3-1. The terminal designated C (Common) corre-
sponds to terminals numbers 23, 25, 27, 29, 31 or 33 on the Rear Programming Connector
NOTE: BOP’S have front and rear output terminals. Only the front terminals are shown on all
subsequent simplified diagrams.
FIGURE 3-1. REAR PROGRAMMING CONNECTOR TERMINALS