BOP 5-20DL 081915
2-3
FIGURE 2-2. BOP TERMINATIONS AND CONTROLS, REAR PANEL
2.3
A-C INPUT REQUIREMENTS
This power supply is shipped wired for operation on a single phase, nominal 115V a-c line. For
operation on other a-c source voltages, refer to FIG. 2-3. Check your prevailing nominal source
voltage and change the links on the barrier strip of T201 according to the table provided in FIG.
2-3. The circuit breaker (CB101) remains equally effective at all input voltages.
FIGURE 2-3. A-C SOURCE VOLTAGE SELECTION
2.4
COOLING
The components in the BOP power supply rely on forced air cooling for the maintenance of their
operating temperature. Side panel openings and the top of the case must be kept clear from all
obstructions to ensure air circulation. Periodic cleaning of the interior of the power supply is rec-
ommended.
If the BOP is rack-mounted or installed into confined spaces, care must be
taken that the ambient temperature (the temperature immediately surrounding the power
supply) does not rise above 55°C (~131°F).
See
Table 2-2
for functions.
FOR AC
SOURCE:
CONNECT LINKS
BETWEEN TERMINALS:
104V
(3)—(4) and (7)—(8)
115V
(4)—(5) and (6)—(7)
208V
(2)—(3) and (8)—(9)
230V
(5)—(6)