30
3. Press the Salinity—Product Button
4. Press Continue to acknowledge the warning
5.
The system will run for a minimum of 5 minutes to stabilize the product water salinity.
6.
Using a calibrated handheld TDS meter measure the salinity of the product water at a
sampling port, or a convenient location if no sampling valve was installed.
7.
Touch the
‘
PPM
’
field and enter the reading taken above.
8.
Press
‘
Proceed
’
to store the new calibration value.
You must save all changes when
prompted after exiting the settings menu
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Salinity Calibration
1. Press the Menu Button
2. Press the Calibrate Sensors Button
The Salinity probe has been calibrated at the factory during testing and is not normally
required during commissioning. If the product quality is not reading accurately, follow
calibration steps.
Summary of Contents for Spectra Catalina 340C
Page 2: ...2...
Page 15: ...15 John Guest Super Speedfit Fittings...
Page 50: ...50 This page intentionally left blank...
Page 64: ...64 Wiring Schematic...
Page 73: ...73 Parts 1...
Page 74: ...74 Parts PL MTS 3 8X1 2B HP CYL SST HP CYL CCA SO HPP ECCB HP CYL EC HP CYL R HP CYL PT Parts...
Page 78: ...78...
Page 80: ...80...
Page 83: ...83...