61
Settings
Dealer Access Settings
It is highly recommended that users consult with a factory trained technician before altering any settings behind
the
‘
Dealer Access Point
’.
Changing this settings without understanding the full effect of each change can void
the warranty of your system, and cause irreparable damage.
If any settings are inadvertently changed, they can be reverted back to the defaults by using the
‘
Factory Reset
’
feature.
Purge Setup:
Adjusts the time and maximum feed pressure allowed for the Purge Mode.
CAUTION: Permanent
damage to the membrane can occur if this setting is adjusted. Consult the factory before making any
adjustments.
Fresh Water Flush Settings:
Allows adjustment of the fresh water flush duration and the interval between
flushes. If the Z
-
Ion is installed, the Flush Interval should be changed to 30 days.
Conductivity Setup:
Allows for enabling or disabling conductivity sensors on the feed water and product water.
Set the threshold for the diversion valve to divert water to the tanks.
Flow Setup:
Allows the user to adjust the flow sensor settings, or disable a flow sensor circuit altogether.
DO
NOT USE THIS SETTING TO CALIBRATE THE PRODUCT FLOW.
Follow instructions on calibrating the flow sensor in
this manual.
Tank Level Monitors:
Enable and disable the Tank Level Sensors, which read the % remaining in the tank, and
the tank switches, which allow the system to turn on/off automatically.
Boost Pressure Setup:
Enable alternate Boost Pressure sensors, change the Low Vacuum Limit, or Boost Pressure
Setpoint.
CAUTION: Permanent damage to the pump can occur if this setting is adjusted. Consult the factory
before making any adjustments.
Low Vacuum Limit:
The minimum boost pressure required at the inlet to the pump. This setting pre
vents the pump from getting damaged by running under high vacuum. Adjusting it to a lower number in
creases the risk that the pump will suffer damage during normal operation.
Boost Pressure Setpoint:
During startup the controller turns on the boost pump and waits for the Boost
Pressure to reach the Boost Pressure Setpoint. If the boost pressure fails to reach this setpoint, then the
main pump won
’
t turn on. Reducing the Boost Pressure Setpoint may cause the system to start, then
immediately shut down due to low boost pressure.
Outlet Pressure Setup:
Set High Pressure Limit, enable alternate high pressure sensors, select pressure sensor
scaling.
CAUTION: Permanent damage to the pump can occur if this setting is adjusted. Consult the factory
before making any adjustments.
Network Setup:
Enabling the Spectra Connect Wireless access turns on a Power Over Ethernet feature on the
wired connection.
ENABLING THIS FEATURE CAN CAUSE SERIOUS DAMAGE TO YOUR SHIP
’
S NETWORK. DO
NOT ENABLE THIS FEATURE WITHOUT CONSULTING A QUALIFIED TECHNICIAN OR THE FACTORY.
Summary of Contents for Spectra Catalina 340C
Page 2: ...2...
Page 15: ...15 John Guest Super Speedfit Fittings...
Page 50: ...50 This page intentionally left blank...
Page 64: ...64 Wiring Schematic...
Page 73: ...73 Parts 1...
Page 74: ...74 Parts PL MTS 3 8X1 2B HP CYL SST HP CYL CCA SO HPP ECCB HP CYL EC HP CYL R HP CYL PT Parts...
Page 78: ...78...
Page 80: ...80...
Page 83: ...83...