SECTION 5
SECTION 5
SECTION 5
SECTION 5
SECTION 5 - - P h y s i c a l C o m p o n e n t s C o n f i g u r a t i o n
- - P h y s i c a l C o m p o n e n t s C o n f i g u r a t i o n
- - P h y s i c a l C o m p o n e n t s C o n f i g u r a t i o n
- - P h y s i c a l C o m p o n e n t s C o n f i g u r a t i o n
- - P h y s i c a l C o m p o n e n t s C o n f i g u r a t i o n
Field Definition
Address
This field identifies the physical address of the module.
Tamper
If selected, the system will generated a Combus module defect
event on the controller, whenever the tamper is disconnected from
the module.
Low Pwr
If selected, the system will generate a Combus module defect event
on the controller, for a lost of power from the module.
AC Fail
If selected, the system will generate a Combus module defect event
on the controller, for a lost of AC power from the module.
Pwr Fail
If selected, the system will generate a Combus module defect event
on the controller, for a lost of power from the module.
Low Aux
If selected, the system will generate a Combus module defect event
on the controller if the voltage of the auxiliary output is too low.
The auxiliary output is used when the module is wired as a
“repower” module, if not, it can be used for other purposes but
there is no control over that output (always activated).
Serial #
Register the serial number of the module, showed in the List of
unassigned components screen.
Functionality
Select the module’s functionality.
Relay 1 to 4 - Will define the 4 relays of the module as a physical
address from 1 to 4 in your software.
Note: All KT-PC4204 modules that are used for Combus repower
should be assigned as relays 1-4.
Relay 5 to 8: Will define the 4 relays of the module as a physical
address from 5 to 8 in your software.
Relay 9 to 12: Will define the 4 relays of the module as a physical
address from 9 to 12, etc.
Important Note: When using the KT-PC4204 in “repower”
mode, the first relay of the module will be reserved for the
“repower function”. You will have to assign an “all valid”
schedule to the first relay so it is “permanently activated”. If you
are using a KT-PC4204 in “repower” mode and other KT-
PC4204 modules that are assigned as relays 1-4 or KT-PC4216
modules that are assigned as relays 1-16 are also connected to
the same loop, do not use relay 1 of those modules or relay 1 of
the KT-300 door controller. Please also note that all KT-PC4204
modules that are used for Combus repower should be assigned
as relays 1-4. The jumper 1 “J1” on the KT-PC4204 must be
moved to the Combus relay position.
Note: Do not use any power supply other than the KT-PC4204
to repower the Combus. In the event of a power surge or transient,
a module may lock up and cease to communicate with the
controller. If the KT-300 loses communication with the module,
it will initiate a module reset and will power down the Combus
for five seconds in attempt to reset the problem module. After five
seconds, the controller will reapply power to the Combus and the
problem module should begin to operate as intended.
KT-PC4216 - 16-zone output expansion module
Field Definition
Address
This field identifies the physical address of the module.
Tamper
If selected, the system will generated a Combus module defect
event on the controller, whenever the tamper is disconnected from
the module.
Low Pwr
If selected, the system will generate a a Combus module defect
event on the controller, for a lost of power from the module.
Serial #
Register the serial number of the module, showed in the List of
unassigned components screen.
Functionality
Select the module’s functionality.
Relay 1 to 16: Will define the 16-zone outputs as a physical
address from 1 to 16 in your software.
Note: If you are using a KT-PC4204 in “repower” mode on the
same loop, do not use the first relay of the KT-PC4216 (see KT-
PC4204).