63
Katherm HK
1.43
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
Parameter P44
Parameter P44 is used to set the function of the digital input DI2 when DIP
switch no. 4 = OFF.
Parameter P56
The polarity of digital input DI2 is set using parameter P56 when setting
DIP switch no. 4 to ON.
The digital input DI1 is predominantly used to execute specific functions. If
the use of the digital input DI2 is needed, then the following settings have
to be made:
1. Set DIP switch no. 4 to OFF.
2. Configuration of the digital input DI2 using parameter settings P44.
20.6.2 Function of DI2
Function
Standar
d
Min
Max
Unit
P44
Function DI2
0 = no function
1 = ON/OFF
(contact open
ON)
2 = Heating/cooling changeover (contact open
heating)
3 = Eco/day mode
(contact open
day)
4 = no function
(contact open
no function)
5 = Condensation alarm
(contact open
no condensation)
6 = General alarm
(contact open
no alarm)
7 = Ext. frost protection monitor (contact open
no frost)
8 = ON/OFF
(contact closed
ON)
9 = Heating/cooling changeover (contact closed
heating)
10 = Eco/Day mode
(contact closed
day)
11 = no function
(contact closed
no function)
12 = Condensation alarm
(contact closed
no condensation)
13 = General alarm
(contact closed
no alarm)
14 = Ext. frost protection monitor (contact closed
no frost)
0
0
14
Function
Standard
Min
Max
Unit
P56
Polarity of DI2 when DIP4 = ON (Heating/cooling
changeover using DI2)
0 = Contact closed
heating
Contact open
cooling
1 = Contact open
heating
Contact closed
cooling
1
0
2
If DIP switch no. 4 is set to ON, digital input DI2 changes over from
heating to cooling in a 2-pipe system.