Katherm HK
1.43
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
Problem
Solution
The fan of a slave unit does not start up.
1. When a clip-on temperature sensor is fitted, the parametrised medium
temperature has not been reached.
2. The room temperature has already reached the setpoint.
=> Check parameter setting.
=> Inform Service personnel if the fan is not activated despite the request to do
so.
The fan does not rotate at the set speed.
1. When a clip-on temperature sensor is fitted, the parametrised medium
temperature has not been reached.
2. Ventilation cycle is in operation
=> Check parameter setting.
=> Inform Service personnel if the fan does not rotate at the desired fan speed
despite the request to do so.
The KaControl-KaControl PCB was not switched on / off at the set time.
Possible power failure.
“Motor fault” message
Check the fan for a blockage
==> Eliminate the cause of the fault.
Disconnect the unit to eliminate the cause of the fault.
“Condensation alarm” message
Check the function of the condensation pump and the water level in the
condensation tray.
=> Check the condensation pump should there be a fault.
=> Check the water train should there be water standing in the condensation
pump.
“EEPROM” message
Reset the parameters to the default values.
Sensor AI1, AI2 or AI3 faulty
Check the sensor values and the electrical connection of the sensors.
16.8 A18 EEPROM error
The EEPROM error is displayed if an error is detected in the internal
memory on the KaControl PCB.
Cause:
Overflow of values, maximum read and write cycles reached.
Effect of this alarm:
Communication in the tLan network and control is interrupted.
16.9 A19 Slave offline in the CAN network
reserved for subsequent use.
16.10 Problem solution