18
1.43
Katherm HK
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
Combination of Katherm HK with supply air trench
(filter optional accessory)
7
6
5
4
2
1
3
8.2 Katherm HK – Supply air ducts ZL
The Katherm supply air trench ZL is available for all
trench heaters (Katherm range). This represents a
400 mm long trench, which can be fitted to all
designs of Katherm units. Treated supply air can
also be fed into rooms through the Katherm supply
air trench ZL. This is achieved with different sizes/
designs of spigots for the most diverse trench
dimensions.
1
Supply air duct with supply air spigots
2
Connecting brackets
3
Supply air slider
4
Reinforcing struts
5
Perforated plate
6
Filter
7
Example of Optiline roll-up grille
Trench
width
Trench
length
Trench
height
Supply air
spigot
Max. air volume
(noiseless)
[mm]
[mm]
[mm]
[mm]
[m³/h]
320
400
130
oval
51x128
70
290
400
160
DN 80
60
360
400
210
DN 100
85
Supply air duct, oval, for Katherm HK 320/130
Side view
Side view
Side view
Supply air duct DN 80 for Katherm HK 290/160
Supply air duct DN 100 for Katherm HK 360/210
Adjusting the slider positions
The supply air model, like all standard Katherm units, is
adjusted in height via the adjustment screws and fixed to
the floor via the adjustment feet. To set the desired flow rate
at the supply air module, you can move the slider in various
positions. The illustration on the left shows 4 different slider
positions (100%, 75%, 50% and 30% open). They are also
shown in the design diagrams below, where you can read off
the desired pressure losses, sound levels and air flow rates.
Intermediate values can be interpolated.
100% 75% 50% 30%