70
1.43
Katherm HK
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
P034
Flushing function: activation in operating modes
0
0
3
-
0
P035
Time the fan runs at Stage 1 after change of operating mode
0
0
255
s
0
P036
Type of setpoint setting
0
0
1
-
0
P037
Display
1
0
7
-
1
P038
Lock/disable function on control unit
64
0
255
-
72
P039
Function of digital output V2 (in 2-pipe system)
0
0
3
-
0
P040
Valve actuation by means of pulse width modulation
0
0
1
-
0
P041
Reset time of PI controller to actuate the fan in automatic fan mode
0
0
20
Min
0
P042
Fan setting: lock and activate fan stages
0
0
127
-
0
P043
Function of digital input DI1
1
0
14
-
5
P044
Function of digital input DI2
0
0
14
-
0
P045
Threshold voltage for potentiometer, which switches on unit
10
0
100
kOhm
10
P046
Temperature setting corresponds to minimum resistance value = 10 kOhm in the potentiometer
18
12
34
°C
18
P047
Temperature setting corresponds to maximum resistance value = 100 kOhm in the potentiometer
24
13
35
°C
24
P048
Threshold voltage for potentiometer for starting up fans
10
0
100
kOhm
10
P049
Threshold voltage for potentiometer for maximum fan speed
90
0
100
kOhm
90
P050
Fan setting: max. fan speed
100
0
100
%
100
P051
Fan setting: min. fan speed
0
0
90
%
0
P052
Fan setting: speed limitation activated
0
0
1
-
0
P053
Valve actuation by pulse width modulation of valve switching cycle
15
10
30
Min
15
P054
Configuration of bus system
0
0
2
-
0
P055
Display of heating/cooling symbols in Automatic mode
0
0
1
-
1
P056
DI2 setting (polarity) when DIP 4 = ON
1
0
1
-
1
P057
Reset setpoint setting to the value of P01 (after changing operating program)
0
0
1
-
0
P058
Sensor calibration: sensor AI1
0
-99
127
K/10
0
P059
reserved
-
-
-
-
-
P060
reserved
-
-
-
-
-
P061
Sensor calibration: sensor in the KaController
0
-99
127
K/10
0
P062
Sensor calibration: sensor AI2
0
-99
127
K/10
0
P063
reserved
-
-
-
-
-
P064
Sensor calibration: sensor AI3
0
-99
127
K/10
0
P065
reserved
-
-
-
-
-
P066
Master/Slave assignment in CAN bus
0
0
1
-
0
P067
CANBus serial address
1
1
125
-
1
P068
Logic of idronic algorithms
0
0
7
-
0
P069
Network address
1
0
207
-
1
P070
Dependence of idronic algorithm (for slave units0
0
0
7
-
0
P071
Serial address of Slave 1
0
0
207
-
0
P072
Serial address of Slave 2
0
0
207
-
0
Summary of Contents for Katherm HK Series