69
Katherm HK
1.43
Ready-to-install trench heaters with EC tangential fan
Assembly and installation instructions
21.2 Parameter list for KaControl PCB
Parameter
Function
Standar
d – V1.9
fr
om July 2011
Min
Max
Unit
Katherm 05.05.2014
SAP: 9000260
P000
Software version
-
0
255
-
-
P001
Base setpoint for setpoint entry ± 3K
22
8
32
°C
22
P002
Switching on / off hysteresis for valves
3
0
255
K/10
1
P003
Neutral zone in a 4-pipe system (only in automatic mode)
3
0
255
K/10
3
P004
Cooling without fan assistance (natural convection)
0
0
255
K/10
0
P005
Heating without fan assistance (natural convection)
5
0
255
K/10
3
P006
Fan On/Off hysteresis (only in ventilation mode)
5
0
255
K/10
5
P007
P-band for heating
15
0
100
K/10
17
P008
P-band for cooling
20
0
100
K/10
20
P009
Offset to the base setpoint for setpoint input ± 3K
3
0
10
K
3
P010
Clip-on sensor: limit temperature to activate fan stages 1 and 2 in heating mode
29
0
255
°C
26
P011
Clip-on sensor: limit temperature to activate fan stages 3 and 4 in heating mode
31
0
255
°C
28
P012
Clip-on sensor: limit temperature to activate fan stage 5 in heating mode
33
0
255
°C
30
P013
Clip-on sensor: hysteresis for limit temperatures P010, P011, P012, P014
10
0
255
K/10
10
P014
Clip-on sensor: limit value temperature to activate the fan stages in cooling mode
18
0
255
°C
18
P015
Function of input AI1
0
0
19
-
0
P016
Function of input AI2
0
0
19
-
0
P017
Function of input AI3
0
0
9
-
0
P018
Raise temperature of cooling setpoint in Eco mode
30
0
255
K/10
30
P019
Lower temperature of heating setpoint in Eco mode
30
0
255
K/10
30
P020
ADC limit coefficient
6
0
15
-
6
P021
ADC average coefficient
6
0
15
-
6
P022
Activation/disabling of sun symbol in Comfort mode
0
0
1
-
0
P023
Difference for compensation during cooling
0
-99
127
K/10
0
P024
Coefficient for compensation during heating
0
-20
20
1/10
0
P025
Difference for compensation during heating
0
-99
127
K/10
0
P026
Coefficient for compensation during heating
0
-20
20
1/10
0
P027
Fan setting: maximum run-time for manual fan mode
0
0
255
Min
0
P028
Flushing function: fan stage during the flushing function
2
1
5
-
2
P029
Activation of continuous fan mode
0
0
1
-
0
P030
Ventilate temperature activation
12
0
255
°C
12
P031
Ventilation interval
27
0
255
°C
27
P032
Flushing function: maximum idle time of fan
15
0
255
Min
15
P033
Flushing function: duration of flushing function
240
0
255
s
240
Summary of Contents for Katherm HK Series