➤ Keep to inspection intervals in accordance with the Ordinance on Industrial Safety and Health
with maximum intervals as laid down in §15.
The inspection intervals are laid down in the technical specification for the air receiver. In‐
spection intervals are dependent on the pressure/volume product of the air receiver, i.e. max
permissible pressure (PS) in bar, times the receiver volume (V) in litres.
Example: volume V = 90 litres, max. permissible pressure PS = 11 bar; pressure/volume
product = 990.
Inspection
Inspection interval
Inspecting authority
Installation and equip‐
ment inspection
Before commissioning if pressure
PS x volume V ≤ 200
Competent person
(e. g. KAESER Service Techni‐
cian)
Compressors with type approval in‐
spection (Ordinance on Industrial
Safety and Health, annex 5 no. 25)
PS x V ≤ 1000
Competent person
(e. g. KAESER Service Techni‐
cian)
Before commissioning if
PS x V > 200
Approved supervisory body
Internal inspection
Every 5 years after installation or the
last inspection if
PS x V ≤ 1000
Competent person
(e. g. KAESER Service Techni‐
cian)
Every 5 years after installation or the
last inspection if
PS x V > 1000
Approved supervisory body
Strength test
Every 10 years after installation or the
last inspection if
PS x V ≤ 1000
Competent person
(e. g. KAESER Service Techni‐
cian)
Every 10 years after installation or the
last inspection if
PS x V > 1000
Approved supervisory body
* The inspection interval is determined by the user in consultation with the approved supervisory
body. The responsible body is to be notified not later than 6 months after the inspection carried
out before commissioning (if pressure x volume V > 1000). Intervals given are the maximum in
each case.
Tab. 23 Inspection intervals according to Ordinance on Industrial Safety and Health
3.5 Dangers
Basic Information
Information concerning the various forms of danger that can arise during machine operation are
found here.
Basic safety instructions are found in this service manual at the beginning of each chapter in the
section entitled 'Safety'.
Warning instructions are found before a potentially dangerous task.
3
Safety and Responsibility
3.5
Dangers
No.: 9_9418 20E
Service Manual Reciprocating compressor
Premium compact W
13
Summary of Contents for Premium Compact W 200/4
Page 2: ...Original instructions KKW PPWCO 2 00 en SBA PREMIUM COMPACT TRAGBAR 20120822 115136 ...
Page 6: ...Contents iv Service Manual Reciprocating compressor Premium compact W No 9_9418 20E ...
Page 10: ...List of Tables viii Service Manual Reciprocating compressor Premium compact W No 9_9418 20E ...