Rated voltage: 400V / 3 / 50Hz
EPC
Current
drawn [A]
Direct start
Star-delta start
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
340-G
4.0
●
10
4 x 1.5
6
4 x 1.5
440-G
5.7
●
10
4 x 1.5
10
4 x 1.5
630-G
6.8
●
16
4 x 2.5
10
4 x 1.5
840-G
10.0
●
20
4 x 2.5
16
4 x 2.5
1100-G
12.0
●
25
4 x 4
16
4 x 2.5
1500-G
18.0
○
35
4 x 6
20
4 x 2.5
● Pressure switch
○ controller (START CONTROL)
Tab. 17 Supply details 400V / 3 / 50Hz
Rated voltage: 500V±10% / 3 / 50Hz
EPC
Current
drawn [A]
Direct start
Star-delta start
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
340-G
3.2
●
10
4 x 1.5
6
4 x 1.5
440-G
4.4
●
10
4 x 1.5
6
4 x 1.5
630-G
5.2
●
10
4 x 1.5
6
4 x 1.5
840-G
8.0
●
16
4 x 2.5
10
4 x 1.5
1100-G
9.6
●
20
4 x 2.5
10
4 x 1.5
1500-G
14.4
○
35
4 x 6
16
4 x 2.5
● Pressure switch
○ controller (START CONTROL)
Tab. 18 Supply details 500V / 3 / 50Hz
Rated voltage: 690V±10% / 3 / 50Hz
EPC
Current
drawn [A]
Direct start
Star-delta start
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
Backup
fuse [A]
Supply ca‐
ble [mm
2
]
340-G
1.8
●
6
4 x 1.5
–
–
440-G
3.3
●
10
4 x 1.5
–
–
630-G
3.9
●
10
4 x 1.5
–
–
840-G
5.8
●
10
4 x 1.5
–
–
1100-G
6.9
●
16
4 x 1.5
–
–
● Pressure switch
○ controller (START CONTROL)
2
Technical Specifications
2.11 Electrical connection
10
Assembly and operating manual 1-stage piston compressor
EPC-G
No.: 9_5752 24 E