Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
Inv. type
Displays the type designation of the device. If feed-in power is actively
limited: display maximum power in kW.
4
1
2
3
SW version
Displays the installed software version.
4
1
2
3
Serial number
Displays the serial number of the device.
4
1
2
3
Select country
Displays the selected country setting. Optional: Displays the grid type if
a grid type has been selected.
4
1
2
3
Vendor
The display shows information about the device manufacturer.
9.4.2
Configuration via web user interface
NOTE
In addition to the parameters in the chapter [See section 9.4.1
Page 36], additional parameters are available
and accessible via the web user interface. To do so, enable
Remote config
in
Network
under
Web-
server
and enter the device IP address into your browser.
4
1
2
3
Operating settings
NOTE: Options for advanced setting of the operating paramet-
ers.
4
1
2
3
DC starting volt.
The device begins feed-in as soon as this DC voltage is present.
F
Set the starting voltage.
4
1
2
3
Const.volt.reg.
NOTE: Option to disable the MPP seek mode in order to oper-
ate the device with a constant DC voltage.
1. Activate or disable the constant voltage controller.
2. Set value for constant voltage controller.
4
1
2
3
Iso.resistance
F
Set threshold value (in 1kOhm increments) at which the insulation
monitor reports a fault.
4
1
2
3
4
3-phase monitoring
On / Off
NOTE: The device is equipped with redundant 3-phase monit-
oring. If the grid voltage exceeds or drops below the con-
figured values, the device switches off. The minimum switch-
off threshold can be set in 1 V increments.
F
Activate or disable monitoring.
4
1
2
3
4
FRT (Fault Ride
Through)
NOTE: The device supports dynamic grid stabilization (Fault
Ride-Through)
.
NOTE: More detailed information at:
4
1
2
3
4
Operation mode –
On | Off
F
Select a control process.
On
: Activates dynamic grid support using dynamic reactive current.
Off
: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Settings | Manual |Pre-
defined zero current
F
Select a control process.
Priority – Reactive cur-
rent limitation | Dy-
namic reactive current
F
Select a control process.
Manual
Configuration and operation | 9
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3