No. Grid
LED
LED
Display
Status description
Action
Pers
.
181
Insulation error, centre
The insulation error is located close to the
centre of a PV string. The area -15% of
the half of the modules based on the total
number of modules. When the insulation res-
istance is distributed equally across the entire
string, this message is also generated when
the calculated insulation resistance falls below
the set value. Insulation error close to the
centre of the PV string (area co-15% of
the half of the string)
Insulation errors
must be rectified in
order to operate
the system safely
and reliably.
B
182
Insulation error, minus
The insulation error is located between the
centre of a string and the minus terminal on
the inverter. If the insulation error is located
very close to the minus inverter terminal, then
the error occurs even if the insulation error
<150 kOhm and is above the set value. Insula-
tion error on the minus terminal side of the PV
string.
See action in the
event of an error
181
B
183
Insulation error, plus
The insulation error is located between the
centre of a string and the plus terminal on the
device. If the insulation error is located very
close to the plus inverter terminal, then the er-
ror occurs even if the insulation error <150
kOhm and is above the set value. Insulation er-
ror on the plus terminal side of the PV string.
See action in the
event of an error
181
B
203
Protection shutdown grid
volt. L1
Protection shutdown grid voltage (effective
value) L1
Incorrect grid
voltage measure-
ment that is outside
the permissible
range. Check the
AC-side wiring (e.g.
increased voltage
due to inductance
capacity of a trans-
former) If the error
display occurs fre-
quently, or every
time, the installa-
tion must be
checked. If the in-
stallation is fault-
free, there is a
device fault. Check
all connection ter-
minals from the
device to the grid
connection. A fluc-
tuating or missing
AC voltage can in-
dicate this connec-
tion problem.
B
204
Protection shutdown grid
volt. L2
See description in the event of an error 203
See action in the
event of an error
203
B
11 | Maintenance and troubleshooting
Manual
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 88
EN
Summary of Contents for blueplanet 15.0 TL3
Page 95: ......