4
1
2
3
4
ROCOF threshold level
1 value 0.1 – 6.0
[Hz / s]
ROCOF threshold level
2 value 0.1 – 6.0
[Hz / s]
F
Define threshold for ROCOF.
ROCOF threshold level
1 time 0.10 – 5.00
[ s]
ROCOF threshold level
2 time 0.10 – 5.00
[ s]
F
Define time value for ROCOF.
4
1
2
3
4
ROCOF proportionality
factor
-5000 – 5000 [
0
/
00
/
Hz]
Status
1. Define the proportionality factor.
2. Confirm the action field.
4
1
2
3
4
Change password for
“installer”
Password of the
logged-on user | New
password for the “in-
staller” access | Con-
firm new password
1. Enter old password.
2. Enter a new, secure password.
3. Confirm and apply new password.
4
1
2
3
4
Change password for
"user"
Password of the
logged-on user | New
password for the
"user" access | Confirm
new password
1. Enter old password.
2. Enter a new, secure password.
3. Confirm and apply new password.
4
1
2
3
4
10 min. mean value
Overvoltage aver-
aging
F
Set the voltage via averaging.
Counter / inverter
voltage drop
F
Set the voltage.
4
1
2
3
4
Overvoltage protection
Transient overvoltage
protection
114,8 – 148,0 [%
Unom]
Password protection
Status
F
Set the transient overvoltage protection.
NOTE: Shutdown carried out within a grid cycle.
1. Activate optional password protection.
2. Confirm the action field.
4
1
2
3
4
Power Limitation
NOTE: The output power of the device can be set permanently
to a lower value than the maximum output power by the in-
ternal power limitation. This may be necessary in order to
limit the maximum power rating of the system at the grid
connection point, upon the grid operator's request.
4
1
2
3
4
Internal
NOTE: Opportunity to limit the power internally More detailed
information at:
Power Limitation
Status
F
Specify the activation status.
9 | Configuration and operation
Manual
KACO blueplanet 15.0TL3 KACO blueplanet 20.0TL3
Page 50
EN