No. Grid
LED
LED
Display
Status description
Action
Pers
.
57
Waiting for reactivation
Waiting time of the device following an error. The devices
switches on after a
country-specific
waiting period.
-
58
Control board overtemp.
The temperature inside the device was too
high. The device shuts down to avoid hard-
ware damage.
Ensure sufficient
ventilation.
E
59
Self test error
A fault occurred during a self-test.
Contact a qualified
electrician!
E
60
Generator voltage too high
Battery voltage too high
The inverter does not begin feeding into the
grid until the PV voltage falls below a specified
value.
-
-
61
External limit x%
The grid operator has activated the external
PowerControl limit. The inverter limits the
power.
-
-
63
Frequency-dependent
power change
The feed-in power is changed linearly over a
certain frequency value. This requirement is
country-dependent. Required response. No in-
dication on display (behaves in the same way
as normal feed-in mode status 4, therefore no
flashing "Feed-in" LED) Can be viewed in ser-
vice log files and via proLOG/portal. When cer-
tain country settings are activated, the fre-
quency-dependent power change is activated.
Normative require-
ment
-
64
Output current limitation
Output current limiting: The AC current is lim-
ited once the specified maximum value has
been reached.
-
-
70
Fan 1 error
The fan is malfunctioning.
Replace defective
fan. See Mainten-
ance and
troubleshooting
chapter.
E
73
Standalone grid err.
Standalone mode was detected.
Is the grid still
present with all
three phases (fuses
tripped)?
E
74
External idle power require-
ment
The grid operator limits the feed-in power of
the device via the transmitted reactive power
factor.
Not an inverter er-
ror! This is a re-
quirement based on
standards
-
75
Self test in progress
No fault message, only a status. Pre-charging
of DC link in progress. Entire self-test sequence
documented in S7.
If, despite adequate
sunlight conditions,
the device remains
in this status per-
manently, then
there is probably a
fault -> arrange for
a service to be car-
ried out
-