FORM 160.75-O1 (309)
27
JOHNSON CONTROLS
6
refrigerant charging
To avoid the possibility of freezing liquid within the
evaporator tubes when charging an evacuated system,
only refrigerant vapor from the top of the drum or cyl-
inder must be admitted to the system pressure until the
system pressure is raised above the point corresponding
to the freezing point of the evaporator liquid. For water,
the pressure corresponding to the freezing point is 8.54
PSIG (58.9 kPa) for R-134a (at sea level).
While charging, every precaution must be taken to prevent
moisture laden air from entering the system. Make up a
suitable charging connection from new copper tubing to
taBle 3 –
REFRIgERANT CHARgE
evap code
cond
code
factory
charged
lbs.
AP
AP, AQ,
AR, AS
828
AQ
794
AR
739
AS
752
CP
Bw, Bx
1525
CQ
1460
CR
1400
CS
1400
CP
CP, CQ,
CR, CS
1221
CQ
1185
CR
1100
CS
1091
DP
DP, DQ,
DR, DS
1628
DQ
1580
DR
1466
DS
1455
EP
EP, EQ,
ER, ES, ET
1721
EQ
1718
ER
1635
ES
1574
ET
1474
EP
Iw, Ix
1805
EQ
1775
ER
1710
ES
1680
ET
1615
FQ
FQ, FR,
FS, FT
2162
FR
2160
FS
2099
FT
1966
gQ
EV, Ew, Ex
1990
gR
1899
gS
1808
evap code
cond
code
factory
charged
lbs.
HQ
FV, Fw, Fx
2626
HR
2506
HS
2385
JP
JP, JQ, JR,
JS
2557
JQ
2401
JR
2143
JS
2051
LQ
LQ, LR, LS
3175
LR
2857
LS
2734
KP
KP, KQ,
KR, KS
K2, K3, K4
2920
KQ
2742
KR
2490
KS
2384
KT
2992
KV
2808
Kw
2571
Kx
2462
K2
3146
K3
3065
K4
2983
K5
3248
K6
3165
K7
3081
MQ
uw, ux
u8, u9
3540
MR
3325
MS
3135
M2
3760
M3
3635
M4
3385
fit between the system charging valve and the fitting on
the charging drum. This connection should be as short as
possible but long enough to permit sufficient flexibility
for changing drums. The charging connection should be
purged each time a full container of refrigerant is con-
nected and changing containers should be done as quickly
as possible to minimize the loss of refrigerant.
Refrigerant may be furnished in cylinders containing
either 30, 50, 125, 1,025 or 1750 lbs. (13.6, 22.6, 56.6,
464 or 794 kg) of refrigerant.
Summary of Contents for York MaxE YK Series
Page 2: ...Page 2 of 2 ...
Page 3: ......
Page 4: ......
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 135: ...JOHNSON CONTROLS FORM 160 75 O1 309 36 SI metric conversion ...
Page 137: ...JOHNSON CONTROLS FORM 160 75 O1 309 38 NOTES ...
Page 138: ...FORM 160 75 O1 309 39 JOHNSON CONTROLS NOTES ...