JOHNSON CONTROLS
FORM 160.75-O1 (309)
22
results
possiBle cause
remedY
1 . s Y m p t o m : a B n o r m a l l Y h i g h d i s c h a r g e p r e s s u r e
Temperature difference between conden-
Air in condenser.
sing temperature and water off condenser
higher than normal.
High discharge pressure.
Condenser tubes dirty or
Clean condenser tubes. Check water
scaled
conditioning.
High condenser water
Reduce condenser water inlet
temperature.
temperature. (Check cooling tower
and water circulation.)
Temperature difference between conden-
Insufficient condensing
Increase the quantity of water through
ser water on and water off higher than
water flow.
the condenser to proper value.
normal, with normal evaporator pressure.
2 . s Y m p t o m : a B n o r m a l l Y l o W s u c t i o n p r e s s u r e
Temperature difference between leaving
Insufficient charge of
Check for leaks and charge
chilled water and refrigerant in evaporator
refrigerant.
refrigerant into system.
greater than normal with high discharge
Variable orifice problem.
Remove obstruction
.
temperature.
Temperature difference between leaving
Evaporator tubes dirty or
Clean evaporator tubes.
chilled water and refrigerant in the evaporator
restricted.
greater than normal with normal discharge
temperature.
Temperature of chilled water too low with
Insufficient load for
Check prerotation vane motor opera-
with low motor amperes.
system capacity.
tion and setting of low water temper-
ature cutout.
3 . s Y m p t o m :
h i g h
e V a p o r a t o r
p r e s s u r e
High chilled water temperature.
Prerotation vanes fail to
Check the prerotation vane motor
open.
positioning circuit.
System overload.
Be sure the vanes are wide open
(without overloading the motor) until
the load decreases.
4. sYmptom: no oil pressure When sYstem start Button pushed
Low oil pressure displayed on control
Oil pump running in wrong
Check rotation of oil pump
center; compressor will not start.
direction.
(Electrical Connections).
Oil pump not running.
Troubleshoot electrical problem
with oil pump VSD.
operational maintenance
taBle 1 –
OPERATION ANALYSIS CHART
section 5 – trouBleshooting
Summary of Contents for York MaxE YK Series
Page 2: ...Page 2 of 2 ...
Page 3: ......
Page 4: ......
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 135: ...JOHNSON CONTROLS FORM 160 75 O1 309 36 SI metric conversion ...
Page 137: ...JOHNSON CONTROLS FORM 160 75 O1 309 38 NOTES ...
Page 138: ...FORM 160 75 O1 309 39 JOHNSON CONTROLS NOTES ...