8-28
8.2.10.
Emergency recall (Fire):
OPTION
DESCRIPTION
UNIT
DM
DESIGNATED
LEVEL
RECALL FLOOR
Enter the designated floor recall level.
n/a
0098
ALTERNATE
LEVEL
RECALL FLOOR
Enter the alternate floor recall level.
n/a
0099
DESIGNATED
LEVEL
REAR DOOR ?
Specify if the designated level has to open the
rear door. (YES = rear) (NO = front).
YES/NO
0148
ALTERNATE
LEVEL
REAR DOOR ?
Specify if the alternate level has to open the rear
door. (YES = rear) (NO = front).
YES/NO
0149
FIRE SIGNALS INPUTS
REVERSING
Reverse or not the fire signals: FS, ALT, FH,
FMR.
YES = input off, turns on fire sequence.
NO = input activated, turns on fire sequence.
YES/NO
0152
ALTERNATE
SIGNAL
INPUT ON DELAY
On delay filter for ALT fire signal (0 to 1.0s)
0.1s
0153
HOISTWAY
FIRE
->
ALTERNATE LEVEL
Floor return selection for hoitsway fire FH:
YES = return to alternate level.
NO = return to designated level.
YES/NO
0056
MACHINE ROOM FIRE
-> ALT LEVEL
Floor return selection for machine room fire
FMR:
YES = return to alternate level.
NO = return to designated level.
YES/NO
0051
RESET PHASE 1
WITHOUT RFP SIG.
If the fire selector does not have a RESET fire
position (RFP input), enter YES. The fire will be
reset when door is opened without any fire
signal activated at the designated level. Some
States in USA need that feature.
YES/NO
0057
PH2,
DOOR
CLOSE
MOMENTARY PRESS.
In phase 2, the fireman does not need to hold the
door close button to close the door. Momentary
pressure. Some States in USA need that feature.
YES/NO
0058
8.2.11.
Emergency power:
OPTION
DESCRIPTION
UNIT
DM
INVERT
GEN1
AND
GEN2 CONTACTS
GEN1 and GEN2 signals input reversing.
YES/NO
0285
NORMAL OPERATION
ON GENERATOR
Normal
operation
on
emergency
power
operation.
YES/NO
0019
Summary of Contents for 2000 Series
Page 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Page 2: ......
Page 5: ......
Page 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Page 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Page 28: ...6 3 Standard tape selector installation ...
Page 44: ...6 19 ...
Page 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Page 60: ...10 2 ...
Page 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...