3-5
I.
CONSTRUCTION MODE:
The "construction" mode deactivates temporarily certain detections to facilitate the elevator car
construction in "inspection" mode. As soon as the elevator controller is placed in "automatic"
mode and that a call has been placed, the "construction" mode will be deactivated automatically
and all signals will be in function.
The elevator controller must be in "inspection" mode
With the controller’s LCD screen:
•
Press "ESC" to return to the main menus.
•
Press "UP/DOWN" keys to select the main menu "OPERATION MODE".
•
Press "ENTER".
•
Press "UP/DOWN" keys to select the sub menu "CONSTRUCTION MODE".
•
Press "ENTER".
•
Press "UP" to activate the Construction mode.
Deactivated Circuits:
•
Low oil detection "BNH".
•
Low pressures switch "LPS".
•
The fire signals are completely deactivated.
•
All the outputs that set off the alarms are deactivated.
J.
Connect the "up" button across "+A" and "PCH" terminals and the "down" button across "+A"
and "PCB". Do not connect "INS" terminal. The INS relay must be off.
K.
At this time, it is not necessary to connect the Low oil detection "BNH" and the low pressures
switch "LPS". They will be adjusted at the final startup.
L.
At this point of the procedure, please verify:
CPU inputs which must be activated:
•
CDC, HDC, LNH, LNB, J9, J10, RPA, REDR.
•
HDL (locked hall door contact if manual door or motorised cam).
Summary of Contents for 2000 Series
Page 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Page 2: ......
Page 5: ......
Page 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Page 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Page 28: ...6 3 Standard tape selector installation ...
Page 44: ...6 19 ...
Page 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Page 60: ...10 2 ...
Page 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...