6-17
•
Leveling magnets (7" north magnet): Bring the car even with the floor. Place the magnet centered
on the steel tape so that the DZO/DZO1 sensors are energized but the LU and LD sensors are not.
The use of two DZO sensors gives the redundancy for the door zone.
•
The table below shows how to install the magnets and has the legend for a barcode up to 7 floors.
Magnets required for the binary
code
Binary
code
P1
P2
P3
Nbr.
Length
(inches)
Floors
1
1
3
2
1
3
3
2
3
4
1
3
5
2
3
6
2
3
7
3
3
P1, P2, P3 = sensors located in the selector tape.
"North" magnets need to be used. The binary code is only validated when sensors are ON and the
elevator is centered to the floor (DZO = ON, DZO1 = ON, LU = OFF, LD = OFF). These
magnets are used to correct the elevator’s position, so it is important that the magnets be correctly
positioned.
WARNING
It is strongly recommended not to secure the magnets immediately to the steel tape. If a
mistake should happen in the positioning, it would still be easy to move the magnets on the
tape. Wait until you have made successful tests before gluing definitely the magnets to the
tape.Magnet installation with the IP8300-TP1 guide:
Automatisation JRT inc. has developed a guide permitting to quickly locate the door zone
magnets (DZO) and binary code magnets (P1 to P3).
P1
P2
P3
Example: 2nd floor
Slide
3 inch magnet
centered with
P2
Summary of Contents for 2000 Series
Page 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Page 2: ......
Page 5: ......
Page 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Page 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Page 28: ...6 3 Standard tape selector installation ...
Page 44: ...6 19 ...
Page 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Page 60: ...10 2 ...
Page 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...