3-3
•
If Solid-State starter (
Siemens
):
When the soft-starter is powered, it automatically detects the connection of the motor
(
IN DELTA
or
IN LINE
). In the
Configuration
menu, the
Rated Amps
parameter
will indicate the type of connection of the motor
Exemple: 30 HP 600 volts 32 amps motor
Rated Amps = 32A
IN LINE
Rated Amps = 18.48A
IN DELTA
(32 amps ÷ 1.732 = 18.48 amps)
In the Parameter menu, adjust the following 2 parameters:
•
Overload Amps
, enter the rated motor current (
FLA
) from the motor’s
nameplate.
•
Starting Amps,
enter 4x the value of the
Overload Amps
parameter.
Exemple: 30 HP 600 volts 32 amps motor
➔
32 X 4 = 128 Amps.
It is very important to validate the 2 parameters above, depending on the
connection of the motor, the soft-starter processor could automatically change
these downwards.
If the UTS output takes too much time to activate when starting the pump, check
the Starting Amps parameter.
C.
Connect pumping unit to the controller (pump motor, valve, etc...)
D.
Connect the main power supply to L1, L2 and L3 terminals from the main switch.
Remove the 3 fuses and measure the voltage.
Summary of Contents for 2000 Series
Page 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Page 2: ......
Page 5: ......
Page 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Page 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Page 28: ...6 3 Standard tape selector installation ...
Page 44: ...6 19 ...
Page 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Page 60: ...10 2 ...
Page 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...