3-4
E.
Measure:
•
Controller power voltage (see drawings)
•
120 VAC between "J" and "N", "JC" and "N".
•
24 VDC between "+A" and "COM", "+AC" and "COM", "+GR" and "COM", ("+DC" and
"COM") (internal voltage), "V+" and "V-" (Victory door operator).
F.
Synchronize the reverse phase module:
•
If Across the Line starter: Synchronize the reverse phase relay (R.P.R.) Yellow and green
lights will turn on as soon as the phases will be in the right sequence.
•
If Star-Delta starter: Synchronize the reverse phase relay (R.P.R.) Yellow and green lights will
turn on as soon as the phases will be in the right sequence.
•
If Solid-State starter (
Benshaw
): Set the parameter P77 (Input Phase Sensitivity) at ABC or
CBA regarding main power phasing.
•
If Solid-State starter (
SSchuh
): Set the DIP Switch #9 (Phase rotation) at ON = ABC
or OFF = CBA regarding main power phasing.
•
If Solid-State starter (
Siemens
): The
Line Rotation
parameter must be set to ABC or CBA
depending on main power phasing (for more details, see the Soft-Starter manual).
G.
If Solid-State starter, read Soft-Start manual for more detail.
H.
If the controller has a thermistor relay TUS, it must be connected to the P1-P2 sensor terminals of
the motor. Reset the relay by pressing the “reset” push button on the relay. The red light should
turn off. If the relay does not reset, the thermistor in the motor may be in trouble. That sensor
must be thermistor type (variable resistor), not thermal contacts however, dry contact.
It’s possible to bypass the motor thermistor sensor, if necessary, by placing a 400 or 500 OHMS
resistor, ¼ or ½ watt, across P1 and P2 terminals.
If the controller has a thermal contact, connect its 2 wires between the input "CT" of the JRT-
CAN-24XXX board and "COM" terminals. See electrical schematics.
Summary of Contents for 2000 Series
Page 1: ...USER S MANUAL HYDRAULIC ELEVATOR CONTROLLER CANBUS PROCESSOR JLL 2000 SERIES VERSION 2 02 000 ...
Page 2: ......
Page 5: ......
Page 17: ...2 1 2 USE OF THE PROGRAMMING CONSOLE PRO01 OU PRO27 Not available ...
Page 25: ...5 1 5 CONTROLLER TYPE Section not applicable ...
Page 28: ...6 3 Standard tape selector installation ...
Page 44: ...6 19 ...
Page 47: ...7 22 7 TERMINAL SPEED REDUCING DEVICE FOR ELEVATOR GREATER THAN 50 MIN Section not applicable ...
Page 60: ...10 2 ...
Page 72: ...10 14 Alarms Description Causes et verifications supplied Check the door opening ...