Jetter AG
Parameterization | 8
User Manual – JXM-IO-E30
43 / 70
Subindex type
Description
Type
Types
of ac-
cess
Unit/
Value range
64
MIN_CURRENT
If the current applied to the
output falls below the set
threshold, this is inter-
preted as a cable break
and the state changed to
Operational
(as of OS
2.05.0.00).
U16
R/W
1 mA
Default is the
minimum pos-
sible value:
■
PWMi-H3
outputs:
200 mA
min.
■
Other out-
puts: min.
500 mA
65
OPENCIRCUIT_
DETECTION
Enables/disables the cable
break detection of a port.
Mode 1
checks once dur-
ing boot whether a load
pulls the output to GND.
Mode 2
additionally
checks in the switched-on
state whether MIN_CUR-
RENT has been under-
shot.
NOTICE! Do not use the
value 2 (permanent cable
break detection) for
PWM outputs and cur-
rent-controlled outputs.
This may lead false cable
break errors.
U16
R/W
0 = No cable
break detec-
tion
1 = Cable
break detec-
tion enabled
in
Pre-Opera-
tional
state
only
2 = Cable
break detec-
tion perma-
nently en-
abled
Default: 1
68
RESOLUTION
Resolution, e.g. at encoder
input
U8
R/W
0 … 2
0 =
1/4 resolution
1 =
1/2 resolution
2 =
Full resolution
Default: 0
Tab. 35:
Parameter