Jetter AG
Parameterization | 8
User Manual – JXM-IO-E30
42 / 70
Subindex type
Description
Type
Types
of ac-
cess
Unit/
Value range
54
CURRENT_CONTROL_P Current control: P parame-
ter
x1000000
U32
R/W
0
…
4294967295
Default:
100000
55
CURRENT_CONTROL_I
Current control: I parame-
ter
x1000000
U32
R/W
0
…
4294967295
Default:
10000
56
CURRENT_CONTROL_D Current control: D parame-
ter
x1000000
U32
R/W
0
…
4294967295
Default: 400
57
MAX_CURRENT
Maximum current that can-
not exceed the specified
value in the interface type.
U16
R/W
1 mA
Default:
■
3 A for
PWMi_H3
■
7 A for
PWM_H7
58
OVERCURRENT_TIME
In the event of overcurrent,
the unit is switched off af-
ter the corresponding time.
U32
R/W
1 ms
Default:
500 ms
59
TIMEOUT_TIME
Sets the TIMEOUT bit in
the status during frequency
measurement, if no signal
change is present. Deter-
mines from when I_DI-
RECTION signals no
movement.
U32
R/W
0
…
4294967295
Default:
1,000 ms
60
CURRENT_
CONTROL_TIME
Cycle time of current con-
trol
U32
R/W
1 ms
Default: 5 ms
61
FILTER_DEEP
Moving average calcula-
tion depth
U32
R/W
1 … 32
Default: 1
62
GATE_TIME
Measuring time of the fre-
quency measurement
U32
R/W
1 ms
Default: 1000
63
MIN_DEVIATION
Minimum deviation for in-
put values (as of OS
2.04.0.00)
U16
R/W
µA or mV
Default for AI:
10