Jetter AG
Parameterization | 8
User Manual – JXM-IO-E30
41 / 70
Subindex
Description
Type
Types of
access
Unit/
Value range
15
I_DUTY_CYCLE
PWM duty cycle
U16
R
1 ‰
16
I_DIGITAL
Digital value
BOO
L
R
0 … 1
17
I_COUNTER
Counter value (free-running
counter)
U32
R
0 …
4294967295
18
I_PERIODIC_TIME Periodic time, the duration of the
period is measured
U32
R
1 µs
19
I_HPULS_TIME
High pulse time, the duration of
the high pulse is measured
U32
R
1 µs
20
I_LPULS_TIME
Low pulse time; the duration of
the low pulse is measured
U32
R
1 µs
22
I_DIRECTION
Current direction
U8
R
0 … 2
0 = none
Movement
1 = forward
2 = backward
Tab. 33:
Input values
Output values
Subindex
Description
Type
Unit/
Value range
30
O_DIGITAL
Digital value
BOOL
0 … 1
31
O_DUTY_CYCLE
PWM duty cycle
U16
1 ‰
32
O_HCURRENT
Set current value (large measur-
ing range)
U16
1 mA
Tab. 34:
Output values
Parameter
Subindex type
Description
Type
Types
of ac-
cess
Unit/
Value range
50
SENSOR_SUPPLY
Associated sensor supply,
which is also monitored.
U16
R/W
0 = OFF
1 =
VEXT_SEN_1
2 =
VEXT_SEN_2
3 =
VEXT_SEN_3
Default: 0
51
PWM_FRQ
PWM frequency
U32
R/W
0.1 Hz
Default: 1 kHz
52
DITHER_FRQ
Dither frequency
U32
R/W
0.1 Hz
Default: 1000
53
DITHER_AMP
Dither amplitude
U16
R/W
0.1 %
Default: 0