With this data you can calculate the following values:
Based on the following table, determine if the layout is
authorised as well as the deflector position:
CO2 must be measured at the terminal during rated operation
and it must be 5.5%. If this is not the case, the deflector
height must be adjusted.
CONNECTING GAS
The appliance is delivered fully equipped with:
-
A burner assembly installed in the combustion
chamber (1)
-
A solenoid valve block and the gas fittings between
the burner and the solenoid valve block (2)
-
A receiver connected to the solenoid valve block (3)
-
A power cord (4)
-
A remote control synchronised with the receiver
After installing the hood and the ducts, it is necessary to
verify again that the valve can move freely. In order to do so,
lift it several times at the maximum from the inside of the
fireplace.
ADJUSTING THE HEIGHT OF THE DEFLECTOR
Depending on the layout and the number of horizontal,
vertical, oblique and elbow pieces, the height of the deflector
in the appliance must be set to one of 6 positions. Position 1
is the most open position (low draw) and position 6 the most
closed position (strong draw).
Adjustment is done by removing the 2 screws from each
bracket, retracting the bracket on the deflector to put it in the
correct position and tightening the screws once more. Do this
on each bracket individually to make it easier.
HOW TO CALCULATE THE DEFLECTOR POSITION
In order to verify and calculate the deflector position, a
sketch of the required layout should be made, and the
following table should be filled in.
Please note that the minimum requirements for configuration
C11 are: 1 vertical metre + 1 elbow at 90
°
+ horizontal
terminal.
Description
Abbreviation
Measured
value
Number of vertical metres
(1)
…. metres
Number of horizontal metres
(2)
…. metres
Number of metres at an angle of 45°
(3)
…. metres
Number of elbows up to 45° (x0.5m)
(4)
…. metres
Number of elbows up to 90° (x1m)
(5)
…. metres
Description
Abbreviation
Results
Total resistance length
= (1)+(2)+(3)+(4)+(5)
L
…. metres
Total vertical length = (1)
V
…. metres
Total horizontal length
= (2)+(3)+(4)+(5)
H
…. metres
Total vertical length minus total
horizontal length = V-H
R
…. metres
Conditions
Layout
Authorisation
Deflector
Position
L > 12
Non authorised
/
V < 1
Non authorised
/
(2) > 3
Non authorised
/
R < -1
Non authorised
/
-1 < R < 0
Authorised
1
0 < R < 1
Authorised
2
1 < R < 2
Authorised
3
2 < R < 3
Authorised
4
3 < R < 4
Authorised
5
4 < R
Authorised
6
Pressure release
valve
Deflector adjustement (x3)
Déflector
6
5
2
4
1
3
1
3
2
4
INSTALLATION OF THE APPLIANCE
1. INSTALLATION INSTRUCTIONS
Summary of Contents for EVA992GAZ
Page 1: ...Mod les MT190408GC MT190408GM JC BORDELET_ZI LHERAT _ 63310 RANDAN 202008_EN...
Page 2: ......
Page 11: ...INSTALLATION OF THE APPLIANCE 1 INSTALLATION INSTRUCTIONS...
Page 14: ......
Page 15: ...Mod les MT190408GC MT190408GM JC BORDELET_ZI LHERAT _ 63310 RANDAN 202008_EN...
Page 24: ......
Page 25: ...Nameplate of your appliance...
Page 26: ...ZI de Lh rat 63310 RANDAN T l 0470561600 Fax 0470561689 www bordelet com...