List of Function Parameters
110
Function
Code
Name
Description
Factory
Setting
Modify LCD Display
P0.04
Frequency B
command source
0:AI2
1:AI4
2:HDI2
0
◎
FREQ
SOURCE B
P0.05
Scale of frequency
B command
0: Maximum frequency
1: Frequency A command
0
○
FREQ B
SCALE
P0.06
Frequency
command selection
0: A
1: B
2: A+B
3: Max
(
A, B
)
0
○
FREQ
SELECTION
P0.07
Maximum
frequency
10.0~400.00Hz
50.00Hz
◎
MAX FREQ
P0.08
Upper frequency
limit
P0.09~P0.07
50.00Hz
○
UP FREQ
LIMIT
P0.09
Lower frequency
limit
0.00Hz~ 0.08
0.00Hz
○
LOW FREQ
LIMIT
P0.10
Keypad reference
frequency
0.00 Hz ~ P0.08
50.00Hz
○
KEYPAD REF
FREQ
P0.11
Acceleration time 0 0.0~3600.0s
20.0s
○
ACC TIME 0
P0.12
Deceleration time 0 0.0~3600.0s
20.0s
○
DEC TIME 0
P0.13
Running direction
selection
0: Forward
1: Reverse
2: Forbid reverse
0
◎
RUN
DIRECTION
P0.14
Carrier frequency 1.0~16.0kHz
Depend
on model
○
CARRIER
FREQ
P0.15
PWM mode
0:Fixed
1:Random
0
○
PWM MODE
P0.16
Carrier frequency
adjust based on
temperature
0: Disabled
1: Enabled
0
◎
AUTO
ADJUST
P0.17
Motor parameters
autotuning
0: No action
1: Rotation autotuning
2: Static autotuning
0
◎
AUTOTUNIN
G
P0.18
Restore
parameters
0: No action
1: Restore factory setting
2: Clear fault records
3:Restore parameters for
injection molding machine
0
◎
RESTORE
PARA
P1 Group: Start and Stop Control
P1.00
Start Mode
0: Start directly
1: DC braking and start
2: Speed tracking and start
0
◎
START
MODE
P1.01
Starting frequency 0.00~10.0Hz
0.00Hz
◎
START FREQ