Detailed Function Description
63
Function
Code
Name
Description
Setting
Range
Factory
Setting
P5.05
S4 Terminal function
Programmable
multifunction terminal
0~55 0
P5.06 S5
Terminal
function
Programmable
multifunction terminal
0~55 0
P5.07
HDI1 terminal
function
Programmable
multifunction terminal
0~55 0
P5.08
HDI2 terminal
function
Programmable
multifunction terminal
0~55 0
P5.09 S6
Terminal
function
Programmable
multifunction terminal
0~55 0
P5.10 S7
Terminal
function
Programmable
multifunction terminal
0~55 0
P5.11 S8
Terminal
function
Programmable
multifunction terminal
0~55 0
Notice: P5.07 is only used when P5.00 is set to be 1 or 3. P5.08 is only used when
P5.00 is set to be 2 or 3.
The meaning of each setting is shown in following table.
Setting
value
Function
Description
0 Invalid
Please set unused terminals to be invalid to avoid
malfunction.
1 Forward
2 Reverse
Please refer to description of P5.13.
3
3-wire control
Please refer to description of P5.13.
4 Jog
forward
5 Jog
reverse
Please refer to description of P8.06~P8.08.
6
Coast to stop
The inverter blocks the output immediately. The motor
coasts to stop by its mechanical inertia.
7 Reset
fault
Resets faults that have occurred. It has the same function
as STOP/RST.
8 Pause
running
When this terminal takes effect, inverter decelerates to
stop and save current status, such as PLC, traverse
frequency and PID. When this terminal takes no effect,
inverter restores the status before pause.
9
External fault
input
Stop the inverter and output a alarm when a fault occurs in
a peripheral device.