Wiring
21
4.4 Specifications of Breaker, Cable, Contactor and Reactor
4.4.1 Specifications of breaker, cable and contactor
Model No.
Circuit
breaker (A)
Input/output cable (mm
2
)
(Coppery wire)
Rated current of
contactor (A)
(380V or 220V)
3AC 220V
±
15%
CHV100-0R7G-2 16
2.5
10
CHV100-1R5G-2 20
4
16
CHV100-2R2G-2 32
6
20
CHV100-004G-2 40
6
25
CHV100-5R5G-2 63
6
32
CHV100-7R5G-2 100
10
63
CHV100-011G-2 125
25
95
CHV100-015G-2 160
25
120
CHV100-018G-2 160
25
120
CHV100-022G-2 200
35
170
CHV100-030G-2 200
35
170
CHV100-037G-2 200
35
170
CHV100-045G-2 250
70
230
3AC 380V
±
15%
CHV100-1R5G-4 16
2.5
10
CHV100-2R2G-4 16
2.5
10
CHV100-004G-4 25
4
16
CHV100-5R5G-4 25
4
16
CHV100-7R5G-4 40
6
25
CHV100-011G-4 63
6
32
CHV100-015G-4 63
6
50
CHV100-018G-4 100
10
63
CHV100-022G-4 100
16
80
CHV100-030G-4 125
25
95
CHV100-037G-4 160
25
120
CHV100-045G-4 200
35
135
CHV100-055G-4 200
35
170
CHV100-075G-4 250
70
230
CHV100-090G-4 315
70
280
CHV100-110G-4 400
95
315
CHV100-132G-4 400
150
380
CHV100-160G-4 630
185
450
CHV100-185G-4 630
185
500
CHV100-200G-4 630
240
580
CHV100-220G-4 800
150x2
630
CHV100-250G-4 800
150x2
700
CHV100-280G-4 1000
185x2
780
CHV100-315G-4 1200
240x2
900