Detailed Function Description
83
The count pulse input channel can be S1~S5 (
≤
200Hz) and HDI.
If function of output terminal is set as preset count reached, when the count value
reaches preset count value (P8.22), it will output an ON-OFF signal. Inverter will clear
the counter and restart counting.
If function of output terminal is set as specified count reached, when the count value
reaches specified count value (P8.23), it will output an ON-OFF signal until the count
value reaches preset count value (P8.22). Inverter will clear the counter and restart
counting.
Notice:
z
Specified count value (P8.23) should not be greater than preset count value
(P8.22).
z
Output terminal can be RO1, RO2 or HDO.
This function is shown as following figure.
Figure 6.22 Timing chart for preset and specified count reached.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.24
Preset running time
0~65535h
0~65535
65535 h
If function of output terminal is set as running time reached, when the accumulated
running time reaches the preset running time, it will output an ON-OFF signal.
Function
Code
Name
Description
Setting
Range
Factory
Setting
P8.25
FDT level
0.00~ P0.07
0.00~ P0.07
50.00Hz
P8.26 FDT
lag
0.0~100.0%
0.0~100.0 5.0%
When the output frequency reaches a certain preset frequency (FDT level), output
terminal will output an ON-OFF signal until output frequency drops below a certain
frequency of FDT level (FDT level - FDT lag), as shown in following figure.