Version 3.05
| Optidrive Eco User Guide |
15
www.invertekdrives.com
Drive Size
X –Above & Below
Y –Either Side
mm
in
mm
in
2 (IP66)
200
5.9
10
0.394
3 (IP66)
200
5.9
10
0.394
4 (IP55)
200
7.9
10
0.394
5 (IP55)
200
7.9
10
0.394
6 (IP55)
200
7.9
10
0.394
7 (IP55)
200
7.9
10
0.394
NOTE
Typical drive heat losses are approximately 2% of the operating load power.
The above dimensions are for guidance only, the operating ambient temperature of the drive MUST be maintained within the specified limits or
allowed derating at all times.
3.9. Guidelines for Mounting (IP66 Units)
Before mounting the drive, ensure that the chosen location meets the environmental condition requirements for the drive shown in
section
.
The drive must be mounted vertically, on a suitable flat surface.
The minimum mounting clearances as shown in the table below must be observed.
The mounting site and chosen mountings should be sufficient to support the weight of the drives.
Using the drive as a template, or the dimensions shown below, mark the locations required for drilling.
Suitable cable glands to maintain the ingress protection of the drive are required. Gland holes for power and motor cables are pre-
moulded into the drive enclosure, recommended gland sizes are shown above. Gland holes for control cables may be cut as required.
ON
OFF
PWR
ON
OFF
PWR
Drive
Size
X
Above & Below
Cable Gland Sizes
mm
in
Frame
Power Cable
Motor Cable
Control Cables
2
200
7.87
2
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
3
200
7.87
3
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
NOTE
Typical drive heat losses are 2% of operating load power.
The above dimensions are for guidance only, the operating ambient temperature of the drive MUST be maintained within the specified limits or
allowed derating at all times.
3
Mech
anical Installation