74
| Optidrive Eco User Guide |
Version 3.05
www.invertekdrives.com
Fault
Code
No.
OLED Message
Description
Corrective Action
tF-
40
Autotune fail 1
Autotune Failed
Measured motor stator resistance varies between phases. Ensure the motor
is correctly connected and free from faults. Check the windings for correct
resistance and balance.
tF-
41
Autotune fail 2
Measured motor stator resistance is too large. Ensure the motor is correctly
connected and free from faults. Check that the power rating corresponds to the
power rating of the connected drive.
tF-
42
Autotune fail 3
Measured motor inductance is too low. Ensure the motor is correctly
connected and free from faults.
tF-
43
Autotune fail 4
Measured motor inductance is too large. Ensure the motor is correctly
connected and free from faults. Check that the power rating corresponds to the
power rating of the connected drive.
tF-
44
Autotune fail 5
Measured motor parameters are not convergent. Ensure the motor is correctly
connected and free from faults. Check that the power rating corresponds to the
power rating of the connected drive.
P-S
45
Incorrect Supply
Phase Sequence
L1-L2-L3 Phase
sequence is incorrect
Applies to Frame Size 8 drives only, indicates that the incoming power supply
phase sequence is incorrect. Any 2 phases may be swapped.
P-o
48
Feedback Pressure
Low
Low Pressure
Detected by Pipe Fill
Function
Check the pump system for leaks for burst pipes.
Check the Pipe fill function has been commissioned correctly (P3-16 & P3-17).
t-P
49
Output Phase Loss
Output (Motor)
Phase Loss
One of the motor output phases is not connected to the drive.
S-F
50
Modbus Comms
fault
Modbus
communication error
detected
S-F
52
Option Module Fault Fitted communication
Module Fault
Internal communication to the inserted Communications Option Module has
been lost. Check the module is correctly inserted.
S-F
53
IO Card Comms
fault
IO card comms trip
Internal communication to the inserted I/O Option Module has been lost.
Check the module is correctly inserted.
S-F
54
BACnet Comms fault BACnet comms loss
trip
A valid BACnet telegram has not been received within the watchdog time limit
set in P5-05.
Check the network master / PLC is still operating.
Check the connection cables.
Increase the value of P5-05 to a suitable level.