9.9. Parameter Group 0 – Monitoring Parameters (Read Only)
Par.
Parameter Name
Units
P0-01
Analog Input 1 Value
%
Displays the signal level applied to analog input 1 (Terminal 6) after scaling and offsets have been applied.
P0-02
Analog Input 2 Value
%
Displays the signal level applied to analog input 2 (Terminal 10) after scaling and offsets have been applied.
P0-03
Digital Input Status
Binary
Displays the status of the drive inputs, including the extended I/O module (if fitted).
1st Entry: 00000 ... 11111. Drive digital Input status. MSB represents digital input 1 / LSB representing digital input 5.
2nd Entry: E 000 ... E 111. Drive Extended (option) Input status. MSB represents digital input 6 / LSB representing digital input 8.
P0-04
Speed Controller Reference
Hz / Rpm
Displays the set point reference input applied to the drive internal speed controller.
P0-06
Digital Speed Reference
Hz / Rpm
Displays the value of the drive internal Motorised Pot (used for keypad) speed reference.
P0-07
Fieldbus Speed Reference
Hz / Rpm
Displays the set-point being received by the drive from the currently active Fieldbus interface.
P0-08
PID Reference
%
Displays the set-point input to the PID controller.
P0-09
PID Feedback
%
Displays the Feedback input signal to the PID controller.
P0-10
PID Output
%
Displays the output level of the PID controller.
P0-11
Motor Voltage
Volts
Displays the instantaneous output voltage from the drive to the motor.
P0-12
Output Torque
Nm
Displays the instantaneous output torque level produced by the motor.
P0-13
Trip Log
%
Displays the last four fault codes for the drive. Refer to section
for further information.
P0-14
Magnetising Current (Id)
Amps
Displays the motor magnetising Current, providing an auto tune has been successfully completed.
P0-16
DC Bus Voltage Ripple
Volts
Displays the level of ripple present on the DC Bus Voltage. This parameter is used by the Optidrive for various internal protection and
monitoring functions.
P0-17
Motor Stator Resistance (Rs)
Ohms
Displays the measured motor stator resistance, providing an auto tune has been successfully completed.
P0-19
Cascade Run Time Log
Hours
Run Time values for variable speed and DOL pumps used in cascade function. 5 entry log.
0 = Master, 1 = DOL1, 2 = DOL2, 3 = DOL3, 4 = DOL4. Clocks can be reset through P8-20, Master Clock Reset.
P0-20
DC Bus Voltage
Volts
Displays the instantaneous DC Bus Voltage internally within the drive.
P0-21
Heatsink Temperature
°C
Displays the Instantaneous Heatsink Temperature measured by the drive.
P0-22
Time Left to Next Service
Hours
Displays the current time period remaining before the next maintenance becomes due. Maintenance interval is based on the value
entered in P6-24 (Maintenance Time Interval) and the elapsed time since the maintenance interval was enabled or reset.
9
Extended P
arameters