Version 3.05
| Optidrive Eco User Guide |
67
www.invertekdrives.com
11.4.2. 200 – 240 Volt, 3 Phase Input Models
Frame
Size
Output
Current
Capacity
Typical Power Rating
Nominal
Input
Current
Fuse or
MCB
(Type B)
Maximum
Cable Size
Maximum Motor
Cable Length
A
kW
HP
A
sq.mm
AWG
m
ft
2
4.3
0.75
1
3.8
10
8
8
100
330
2
7
1.5
2
6.3
10
8
8
100
330
2
10.5
2.2
3
9.6
16
8
8
100
330
3
18
4
5
14
16
8
8
100
330
3
24
5.5
7.5
21.6
25
8
8
100
330
4
30
7.5
10
27
32
16
5
100
330
4
46
11
15
41.4
50
16
5
100
330
5
61
15
20
48.2
63
35
2
100
330
5
72
18.5
25
58
80
35
2
100
330
5
90
22
30
75.9
100
35
2
100
330
6
110
30
40
126.7
160
150
300MCM
100
330
6
150
37
50
172.7
200
150
300MCM
100
330
6
180
45
60
183.3
250
150
300MCM
100
330
7
202
55
75
205.7
250
150
300MCM
100
330
7
248
75
100
255.5
315
150
300MCM
100
330
11.4.3. 380 – 480 Volts, 3 Phase Input Models
Frame
Size
Output
Current
Capacity
Typical Power Rating
Nominal
Input
Current
Fuse or
MCB
(Type B)
Maximum
Cable Size
Maximum Motor
Cable Length
A
kW
HP
A
sq.mm
AWG
m
ft
2
2.2
0.75
1
2
10
8
8
100
330
2
4.1
1.5
2
3.7
10
8
8
100
330
2
5.8
2.2
3
5.2
10
8
8
100
330
2
9.5
4
5
8.6
10
8
8
100
330
3
14
5.5
7.5
12.4
16
8
8
100
330
3
18
7.5
10
14
16
8
8
100
330
3
24
11
15
21.6
25
8
8
100
330
4
30
15
20
27
32
16
5
100
330
4
39
18.5
25
35.1
40
16
5
100
330
4
46
22
30
41.4
50
16
5
100
330
5
61
30
40
48.2
63
35
2
100
330
5
72
37
50
58
80
35
2
100
330
5
90
45
60
75.9
100
35
2
100
330
6
110
55
75
112.5
125
150
300MCM
100
330
6
150
75
100
153.2
200
150
300MCM
100
330
6
180
90
150
183.7
250
150
300MCM
100
330
7
202
110
175
205.9
250
150
300MCM
100
330
7
240
132
200
244.5
315
150
300MCM
100
330
7
302
160
250
307.8
400
150
300MCM
100
330
8
370
200
300
370
500
240
450MCM
100
330
8
450
250
350
450
500
240
450MCM
100
330
11
Technical Data