11. Technical Data
11.1. Environmental
Ambient Temperature Range
Storage
All
-40 °C … 60 °C
Operational
IP20
-10 … 50°C without derating
IP55
-10 … 40°C without derating
IP66
Maximum Altitude
Operational
All
1000m without derating
Relative Humidity
Operational
All
=< 95% (no condensation permitted)
on page 71 for derating information.
11.2. Input Voltage Ranges
Depending upon model and power rating, the drives are designed for direct connection to the following supplies:
Model Number
Supply Voltage
Phases
Frequency
ODV-3-x2xxxx-1xxx-xx
200 – 240 Volts + / - 10%
1
50 – 60 Hz
ODV-3-x2xxxx-3xxx-xx
200 – 240 Volts + / - 10%
3
50 – 60 Hz
ODV-3-x4xxxx-3xxx-xx
380 – 480 Volts + / -10%
3
50 – 60 Hz
ODV-3-x5xxxx-3xxx-xx
480 – 525 Volts + / - 10%
3
50 – 60 Hz
ODV-3-x6xxxx-3xxx-xx
500 – 600 Volts + / - 10%
3
50 – 60 Hz
11.3. Phase Imbalance
All three phase Optidrive Eco units have phase imbalance monitoring. The maximum permissible voltage imbalance between any two
phases is 3% for full load operation.
11.4. Output Power and Current ratings
The following tables provide the output current rating information for the various Optidrive Eco models. Invertek Drives always
recommend that selection of the correct Optidrive is based upon the motor full load current at the incoming supply voltage.
Please note that the maximum cable length stated in the following tables indicate the maximum permissible cable length for the drive
hardware and does not take into consideration EMC compliance.
11.4.1. 200 – 240 Volt, 1 Phase Input Models
Frame
Size
Output
Current
Capacity
Typical Power Rating
Nominal
Input
Current
Fuse or
MCB
(Type B)
Maximum
Cable Size
Maximum Motor
Cable Length
A
kW
HP
A
sq.mm
AWG
m
ft
2
4.3
0.75
1
8.5
10
8
4.3
100
330
2
7
1.5
2
15.2
25
8
7
100
330
2
10.5
2.2
3
19.3
25
8
10.5
100
330